Copyright ©2012 E. I. du Pont de Nemours and Company. All Rights Reserved. Rev. 2/12 10
DuPont
Tyvek
®
Water-Resistive and Air Barriers Installation Guidelines
Facade Considerations
Water-resistive barrier performance is dependent upon the ability of the facade to drain. The
following must be considered for specific facades.
Stucco
When stucco is installed over wood-based sheathing, the 2009 International Building Code (Section 2510.6) and the 2009
International Residential Code (Section R703.6.3) require “a water-resistive vapor-permeable barrier with a performance
at least equivalent to two layers of Grade D paper” or a layer of water-resistive barrier (WRB) which is separated from the
stucco by an “intervening layer”. When DuPont
Tyvek
®
water-resistive barriers are used behind stucco they should be
separated from the stucco by a second layer of DuPont
Tyvek
®
WRB, a layer of Grade D building paper, felt, rigid foam
board or the paper backing of paper-backed lath. The first layer (directly over sheathing or studs) serves as the wall
system’s water-resistive barrier and is integrated with window and door flashings, the weep screed at the bottom of the
wall and any through-wall flashings or expansion joints. Lath shall be installed over the intervening layer in accordance
with ASTM C1063-03 Standard Specification for Installation of Lathing and Furring to Receive Interior and Exterior
Portland Cement-Based Plaster and applicable codes. Rigid foam board, when installed over DuPont
Tyvek
®
WRB as an
intervening layer, will provide enhanced structural support to the DuPont
Tyvek
®
layer WRB and may reduce the required
number of fasteners used for the attachment of the DuPont
Tyvek
®
WRB if installed as soon as practically possible.
Brick
The 2009 International Residential Code (Section R703.7.4.2) requires a nominal 1 inch airspace separating the brick from
the water-resistive barrier (WRB). The Brick Industry Association recommends a 1 inch air-space in front of wood stud
construction and a 2 inch air-space in front of steel stud construction. Consistent with these requirements and
recommendations, DuPont
Tyvek
®
WRBs shall be separated from the brick veneer by a nominal 1 inch air-space. Window
and door flashing, and through-wall flashing shall be integrated with the DuPont
Tyvek
®
WRB layer ensuring proper
shingling. For maximum moisture management and drying of the wall system the airspace in front of the DuPont
Tyvek
®
WRB shall be vented to the exterior at the top and bottom of the wall. Some types of brick ties will act as additional
fasteners for DuPont
Tyvek
®
WRBs, and, if installed as soon as practically possible after the DuPont
Tyvek
®
WRB, may
reduce the required number of fasteners used for the initial attachment of the DuPont
Tyvek
®
WRB. DuPont
StuccoWrap
®
, DrainWrap
®
or CommercialWrap
®
D are recommended for this application and meet drainage
requirements for one coat stucco and EIFS systems.
Stone Veneer
The 2009 International Building Code (Section 1405.7) requires two layers of water-resistive barrier (WRB) behind stone
(natural, manufactured, synthetic) veneers over wood frame construction. When DuPont
Tyvek
®
WRBs are used behind
stone veneer, they should be separated from the stone and mortar by a second layer of DuPont
Tyvek
®
WRB, a layer of
grade D building paper, felt, rigid foam board or the paper backing of paper-backed lath. The first layer (directly over
sheathing or studs) serves as the wall system’s water-resistive barrier and shall be integrated with window and door
flashings, the weep screed at the bottom of the wall and any through-wall flashings or expansion joints. When rigid foam
board is used as the second layer, it is installed in front of the DuPont
Tyvek
®
WRB. DuPont
StuccoWrap
®
, DrainWrap
®
or CommercialWrap
®
D is recommended for this application.
Wood Siding
DuPont
Tyvek
®
water-resistive barriers (WRB) and wood siding shall be installed according to manufacturer’s
instructions, industry standards and applicable codes. As recommended by the Western Red Cedar Lumber Association
and U. S. Forest Product Laboratory, wood siding should be primed on all six sides before installation. Foam sheathing
panels often have low vapor permeability, and therefore can cause moisture to accumulate on the back of siding and
cause staining, buckling and damage to finish coats. As a result, the Western Red Cedar Lumber Association and other
wood siding manufacturers recommend that furring strips are used to create an air space between foam sheathing and
siding. Other recommendations that should be followed to minimize potential problems are:
• Usethickersidingpatternsinwidthsof8inchesorless.Thick,narrowsidingismorestablethanthinner,wider
patterns and better able to resist dimensional changes.
• Usekiln-driedsidingoverrigidfoamsheathing.
• Properpre-nishingisessential.
• Uselightcolornishcoatstomaximizeheatreectionandreducedimensionalmovement.
• Inallcasesitisrecommendedthathousewrap,suchasDuPont
Tyvek
®
DrainWrap
®
, be applied over the foam
sheathing.
In high exposure installations, enhanced drainage and water management may be provided by using DuPont
Tyvek
®
DrainWrap
, by installing a drainage mesh over the water-resistive barrier, or by creating rainscreen cladding with a
larger airspace behind the siding using furring strips. If furring is installed over the DuPont™ Tyvek
®
WRB to create a
rainscreen,theprimaryfastenerspacingcanexceed18”.
Fiber Cement Siding
DuPont
Tyvek
®
WRBs and fiber cement siding shall be installed according to manufacturer’s instructions and industry
standards. In high exposure installations, enhanced drainage and water management may be provided by using DuPont
Tyvek
®
DrainWrap™, by installing a drainage mesh over the water-resistive barrier, or by creating rainscreen cladding
with a larger airspace behind the siding using furring strips. If furring is installed over the DuPont™ Tyvek
®
water-resistive
barriertocreatearainscreen,theprimaryfastenerspacingcanexceed18”.Inhighwindareasatgableendwalls,FEMA
recommends fiber cement siding be installed over wood sheathing rather than over plastic foam sheathing. DuPont
Tyvek
®
WRBs and fiber cement siding shall be installed according to manufacturer’s instructions, industry standards and
applicable codes.
Vinyl Siding
Vinyl Siding is installed directly over DuPont
Tyvek
®
WRBs. Vinyl siding shall be installed in accordance with
manufacturer’s instructions, industry standards and applicable codes, including ASTM D4756-06 Standard Practice for
Installation of Rigid Poly(Vinyl Chloride) (PVC) Siding and Soffit. In high wind areas at gable end walls, FEMA recommends
vinyl siding be installed over wood sheathing rather than over plastic foam sheathing.